T-ZACCS +
T-ZACCS+ Alarm Unit AL-360
The alarm output function monitors a specified channel and closes the specified contact when the measured value changes by a certain amount (relative value setting) or exceeds a threshold value (upper and lower limit setting).
Monitoring compares and switches contacts when monitoring or scanning is performed. There are four output contacts, and the comparison channel, comparison conditions, and output destination contact can be set.
It is also possible to set a single contact for multiple channels and close the contact if any of them exceeds the set range.

- Features
- Any monitoring channel and any output contact (1 to 4) can be set
- Relative values and upper and lower limit conditions can be set
- Selectable monitored value from monitor value and scan value
-
Specifications
Number of contact points 4 Contact point Semiconductor relay (a-contact: normally open)
Contact capacity
140V AC / 200V DC MAX
Rated current 0.6A MAX
Inrush current 1.8A MAX
ON resistance 2Ω MAXDisplay Status LED
Lights up when each contact is closedComparison method Relative value, upper/lower bounds Number of setting tables 1000 Other Function Alarm test Power Supplied via TS-360 Operating temperature and humidity range -10 to +50°C
85%RH or less (excluding condensation)External dimensions 280(W)×45(H)×60(D)mm
(excluding rubber protectors and protrusions)Weight Approx. 600g